C106 Keypad
Symptom Possible Cause/Remedy
29
The lock release fails to
operate when the Test button
is pressed
Ž Check the lock release and its wiring
by moving the lock connections to
+ C, -H, (forcing the lock)
Ž Measure the voltage on the FAIL
SECR terminals; this should be the
same as the power supply (13.8V)
while the test button is pressed.
Lock release does not
operate when Exit Button is
pressed.
Ž Test by applying a short-circuit directly
to the ‘EXIT’ terminals; Check
connections to Exit button.
Lock operates from the test
button but does not operate
when the code is entered.
Ž Check C106 Keypad is correctly
programmed; Restore to Factory
Settings (page 22, 30);
Ž Time Clock in wrong state; reprogram
action code, manually switch the time
clock.
Lock release is permanently
active
Ž ‘EXIT’ terminals are short-circuited;
temporarily remove connections to
‘EXIT’ and re-test unit.
C106 Keypad
30
Programming the Factory Settings with the Test Button
In the event of any problems, always return to Factory Settings. If the security
key has been forgotten, the test button can be used to restore factory settings.
In the case of a fault disconnect the lock release, before following this procedure.
This operation will restore all codes, times and functions to the factory settings
(see Table 1 page 23 for the complete list).
This facility is useful for fault diagnosis. It makes use of the Test Button on the
C106 Keypad. It is always advisable to return to this condition whenever the unit
appears to malfunction during installation or following an unsuccessful
programming session.
To program Factory Settings:
— Press and hold the TEST
button.
— Observe the red and green
LEDs come on (5 seconds).
— Observe the red and green
LEDs alternating (3 seconds).
— Finally the red and green LED will flash for 1 second and
extinguish. The Factory setting are now programmed; release the
TEST button.